KRAUS EDWARD HENRY BUILDING
Building #
211, Building area is 182,967 Sq. Ft.
In FY09 the total energy expense was $1,369,621 |
  |
 |
|
Current Energy Information
(Click boxes for detail)
|
Historical Energy Information
(Click boxes for detail)
|
|
|
| Electric |
| Electric Expense |
| Steam |
| Steam Expense |
| Gas |
| Gas Expense |
| Water |
| Water Expense |
| Cost | |
|
|
|
|
|
Energy Conservation Measures
|
Green Lights (2000)
Replaced fluorescent ballasts and fluorescent lamps with high efficiency equipment.
Electricity: 481,121 kWh/yr
Annual Savings: $39,452 |
|
VAV box conversion (2000)
Retrofitted the existing pneumatic variable air volume (VAV) boxes that serve the auditorium (Rm. #2140) to direct digital control (DDC).
Electricity: 50,758 kWh/yr
Steam: 50 MLB/yr
Chilled Water: 26 MMBtu/yr
Annual Savings: $5,060 |
|
Addition of VFDs to CHW pumps (2001)
Installed variable frequency drives (VFDs) on the existing secondary chilled water pumps (P-1, 2 and 3) and close the existing balancing valves on fan coil units.
Electricity: 91,751 kWh/yr
Annual Savings: $8,250 |
|
AHU Upgrade (2004)
Replacement of the 2-position motorized dampers (and manual dampers) with 2-position variable air volume (VAV) boxes on the main air handling systems (M-1, M-2 and M-3).
Electricity: 134,940 kWh/yr
Steam: 4,980 MLB/yr
Annual Savings: $66,640 |
|
Insulation of Steam Flash Tanks/Piping (2006)
Installed insulation on the existing steam flash tank and miscellaneous piping located in the supply fan # 3 room.
Steam: 158 MLB/yr
Annual Savings: $2,950 |
|
Occupancy Sensor (2006)
Installed occupancy sensors in various lab rooms to turn off lights when not occupied.
Electricity: 105,441 kWh/yr
Annual Savings: $5,276 |
|
Water Conservation (2006)
Replaced an existing fan-coil unit in one of the laboratory spaces (Rm. #3042) in the Kraus Building (Bldg. #211). This fan-coil unit has a water-cooled condensing unit which is currently using city water in a once-through application.
Water: 885 CCF/yr
Sewer: 885 CCF/yr
Annual Savings: $3,816 |
|
Reducing Autoclave Trap Cooling Water (2007)
Reduced the amount of water being used to cool the condensate on the autoclave units in the prep rooms in the E. H. Kraus Building.
Steam: 34 MLB/yr
Water: 450 CCF/yr
Sewer: 450 CCF/yr
Annual Savings: $11,500 |
| Environmental Quality: The Environmental Protection Agency (EPA) reports that annual energy savings translate directly to reductions in the emissions of certain gases into the atmosphere. The Energy Conservation Measures implemented in this building have saved 8,197 MMBtu/yr. These measures will reduce 2,388 tons of Carbon Dioxide (CO2), 19,026 lbs of Sulfur Dioxide (SO2), and 9,129 lbs of Nitrogen Oxides (NOX) annually. This is equivalent to carbon sequestration of 652 acres of forest land or taking 478 cars off the road. |
|