Energy Conservation Measures
|
Addition of VFDS to HHW Pumps (1999)
Added VFD's to two (2) hot water pumps..
Electricity: 173,366 kWh/yr
Annual Savings: $11,700 |
|
Carbon dioxide sensor for lecture hall (1999)
Installed CO2 sensor in return air duct from Chem 1800.
Chilled Water: 162 MMBtu/yr
Annual Savings: $1,800 |
|
Green Lights (2000)
Installed 7,760 electronic ballasts and 15,226 T-8 style lamps.
Electricity: 1,034,376 kWh/yr
Annual Savings: $85,853 |
|
Modification of outdoor air intake (2000)
Installed new intake louvers to allow less restricted airflow into '88 building AH's.
Electricity: 351,921 kWh/yr
Annual Savings: $28,860 |
|
Sash stop and rebalance project (2001)
Installed sash stop to limit sash travel to 14". Will reduce energy consumption by limting exhaust of conditioned air. Also installed VAV box controllers.
Steam: 2,618 MLB/yr
Chilled Water: 1,373 MMBtu/yr
Annual Savings: $42,660 |
|
Addition of VFDs to HHW pumps (2001)
Installed VFD's on pumps P1 and P2 for the HHW system.
Electricity: 108,355 kWh/yr
Annual Savings: $9,150 |
|
Upgrade of AHU systems (2001)
Rescheduling and installation of VAV boxes and VFD's to some Lecture Hall (1200,1210,1300,1400) AH's.
Electricity: 94,932 kWh/yr
Steam: 1,184 MLB/yr
Annual Savings: $17,465 |
|
Zone isolation dampers (2001)
Installed controls to VAV boxes serving office fan coil units in '48 section.
Electricity: 33,552 kWh/yr
Steam: 9 MLB/yr
Chilled Water: 14 MMBtu/yr
Annual Savings: $4,905 |
|
Exhaust fan staging (2001)
Installed airflow measuring probes that would allow the exhaust fans (EF-48, 49, 50 and 51) serving the ?48 building of the Chemistry Building to be staged based on demand.
Electricity: 56,400 kWh/yr
Annual Savings: $3,860 |
|
Fume hood controls (2001)
Installed fume hood controls on hoods in the '08 and '48 sections. Allows hoods to be completely scheduled off instead of being put on "low" mode.
Chilled Water: 1,347 MMBtu/yr
Annual Savings: $6,450 |
|
Water cooled equipment water conservation (2005)
Converted 3 water cooled chillers to run on building CHW loop, instead of once through city water.
Steam: 7,890 MLB/yr
Water: 1,831 CCF/yr
Sewer: 1,831 CCF/yr
Annual Savings: $7,090 |
|
Cold Room water conservation (2005)
Upgraded the valves and controls on the existing water-cooled condensing unit serving the cold room in Rm. #2713 in the Chemistry Building (1988). Eliminates city water usage..
Water: 1,328 CCF/yr
Sewer: 1,328 CCF/yr
Annual Savings: $5,610 |
| Environmental Quality: The Environmental Protection Agency (EPA) reports that annual energy savings translate directly to reductions in the emissions of certain gases into the atmosphere. The Energy Conservation Measures implemented in this building have saved 20,921 MMBtu/yr. These measures will reduce 6,094 tons of Carbon Dioxide (CO2), 48,560 lbs of Sulfur Dioxide (SO2), and 23,299 lbs of Nitrogen Oxides (NOX) annually. This is equivalent to carbon sequestration of 1,663 acres of forest land or taking 1,219 cars off the road. |
|